アトリウムの温熱環境の実測 : 大きなトップライトをもつ場合
https://kougei.repo.nii.ac.jp/records/256
https://kougei.repo.nii.ac.jp/records/256ab7b497c-c76a-4ed9-85c6-46fa13dbfa6c
名前 / ファイル | ライセンス | アクション |
---|---|---|
![]() |
|
Item type | [ELS]紀要論文 / Departmental Bulletin Paper(1) | |||||
---|---|---|---|---|---|---|
公開日 | 2017-04-21 | |||||
タイトル | ||||||
タイトル | アトリウムの温熱環境の実測 : 大きなトップライトをもつ場合 | |||||
タイトル | ||||||
タイトル | FIELD MEASUREMENTS OF THERMAL ENVIRONMENT IN ATRIUM WITH A LARGE TOP-LIGHT | |||||
言語 | en | |||||
言語 | ||||||
言語 | jpn | |||||
資源タイプ | ||||||
資源タイプ識別子 | http://purl.org/coar/resource_type/c_6501 | |||||
資源タイプ | departmental bulletin paper | |||||
雑誌書誌ID | ||||||
収録物識別子タイプ | NCID | |||||
収録物識別子 | AN00159741 | |||||
論文名よみ | ||||||
タイトル | アトリウム ノ オンネツカンキョウノ ジッソク : オオキナ トップライト オ モツ バアイ | |||||
著者 |
鯉渕, 健造
× 鯉渕, 健造× 小林, 信行× 田中, 幸彦× KOIBUCHI, Kenzo× KOBAYASHI, Nobuyuki× TANAKA, Yukihiko |
|||||
著者所属(日) | ||||||
東京工芸大学工学部建築学科 | ||||||
著者所属(日) | ||||||
東京工芸大学工学部建築学科 | ||||||
著者所属(日) | ||||||
(株)フジタ技術研究所 | ||||||
記事種別(日) | ||||||
内容記述タイプ | Other | |||||
内容記述 | 論文 | |||||
記事種別(英) | ||||||
内容記述タイプ | Other | |||||
内容記述 | Article | |||||
抄録(英) | ||||||
内容記述タイプ | Other | |||||
内容記述 | Thermal environment in the atrium with a large movable top-light have been studied by measuring the temperature distributions and PMV for various air-conditioning conditions. These field measurements were conducted in summer, autumn and winter. In winter, the influence of the cold air penetration from the entrance on temperature condition were also examined. The temperature in the atrium was strongly influenced by the solar radiation in every season and the stagnant air layer with high temperature arose in the upper part of the atrium, especially in summer. When the top- light roof was opened, the stagnant thermal layer was removed and relatively comfortable condition was achieved in the atrium. Under the normal air-conditioning, thermal environment conditions in the occupied zone were shown as "relatively warm" in summer, "neutral" in autumn and "neutral" in winter by the measurement of PMV. In winter, the air temperature in the occupied zone dropped by 7 to 8℃ due to the cold air penetrated from the entrance while five people were passing through the entrance doors. Six minutes was nearly required to recover the level of the former comfortable indoor temperature. | |||||
書誌情報 |
東京工芸大学工学部紀要 en : The Academic Reports, the Faculty of Engineering, Tokyo Polytechnic University 巻 18, 号 1, p. 43-51, 発行日 1995 |
|||||
表示順 | ||||||
内容記述タイプ | Other | |||||
内容記述 | 8 | |||||
アクセション番号 | ||||||
内容記述タイプ | Other | |||||
内容記述 | KJ00001512031 | |||||
ISSN | ||||||
収録物識別子タイプ | ISSN | |||||
収録物識別子 | 03876055 |