タイトル | ||||||
タイトル | 大空間の暖房時の空気分布の実測 | |||||
タイトル | ||||||
タイトル | Field measurements of space air distribution in large spaces under heating conditions | |||||
言語 | en | |||||
言語 | ||||||
言語 | jpn | |||||
資源タイプ | ||||||
資源タイプ識別子 | http://purl.org/coar/resource_type/c_6501 | |||||
資源タイプ | departmental bulletin paper | |||||
雑誌書誌ID | ||||||
収録物識別子タイプ | NCID | |||||
収録物識別子 | AN00159741 | |||||
論文名よみ | ||||||
タイトル | ダイクウカン ノ ダンボウジ ノ クウキ ブンプ ノ ジッソク | |||||
著者 |
小林, 信行
× 小林, 信行× 鯉渕, 健造× 武藤, 清× KOBAYASHI, Nobuyuki× KOIBUCHI, Kenzo× MUTOH, Kiyoshi |
|||||
著者所属(日) | ||||||
東京工芸大学工学部建築学科 | ||||||
著者所属(日) | ||||||
東京工芸大学工学部建築学科 | ||||||
著者所属(日) | ||||||
(株)岡田新一設計事務所 | ||||||
記事種別(日) | ||||||
内容記述タイプ | Other | |||||
内容記述 | 論文 | |||||
記事種別(英) | ||||||
内容記述タイプ | Other | |||||
内容記述 | Article | |||||
抄録(英) | ||||||
内容記述タイプ | Other | |||||
内容記述 | Large vertical temperature gradients are generally liable to occur in the large, high ceiling spaces which are heated with warm air diffusion only. Two types of air diffuser systems have been designed to prevent these temperature gradients. 0ne of the systems is a combination of the floor pannel heater and the outlets mounted in the sidewall that discharge warm air horizontally. The other system is a combination of the horizontal jets as mentioned above, and the outlets mounted in the floor that discharge air vertically. We have carried out the field measurements of the temperature and the velocity distributions in the space which are formed by each of these heating systems and have confirmed that both systems are effective to eliminate the vertical temperature gradient in the occupied zone as compared with the system that only discharges air horizontally. The heating system with the outlets mounted in the floor, in particular, is very useful for heating the occupied zone. | |||||
書誌情報 |
東京工芸大学工学部紀要 en : The Academic Reports, the Faculty of Engineering, Tokyo Polytechnic University 巻 11, 号 1, p. 61-68, 発行日 1988 |
|||||